13.2 Temperature Controller/Servo/Inverter Connection 13-49
PLC_CTL
Macro command “PLC_CTL F0 F1 F2”
Return data: Data stored from temperature controller to V series
*1 8000 (HEX): broadcasting
*2 Valid only for the product of pulse output type or analog output type
Contents F0 F1 (= $u n) F2
Controller status read out
1 - 8
(PLC1 - 8)
n Station number
2
n + 1 Command: 06H
n + 2
Operation status (higher byte)
00: Control in execution for all channels
(Operation in progress while the setting area is “0” with no
error occurring.)
01: Control stopping at any of the channels
(Other than above)
Related information (lower byte)
Operation instructions
1 - 8
(PLC1 - 8)
n
Station number
*1
3
n + 1 Command: 0030H
n + 2
Communication writing
0000H: Communication writing OFF (disabled)
0001H: Communication writing ON (enabled)
Control start/stop
0100H: Channel 1 run
0101H: Channel 1 stop
0110H: Channel 2 run
0111H: Channel 2 stop
01F0H: All-channel run
*2
01F1H: All-channel stop
*2
Multi-SP
0200H: Channel 1 target value 0
0201H: Channel 1 target value 1
0210H: Channel 2 target value 0
0211H: Channel 2 target value 1
02F0H: All-channel target value 0
*2
02F1H: All-channel target value 1
*2
AT execution
0300H: Channel 1 AT execute
0301H: Channel 1 AT cancel
0310H: Channel 2 AT execute
0311H: Channel 2 AT cancel
03F0H: All-channel AT execute
*2
03F1H: All-channel AT cancel
*2
Write mode
0400H: Backup mode
0401H: RAM write mode
0500H: Save RAM data
0600H: Software reset
0700H: Move to set area 1
0800H: Move to protection level
Auto/manual
0900H: PV hold
0B00H: Initialize
Unlatch
0C00H: Channel 1 warning 1 unlatch
*2
0C01H: Channel 1 warning 2 unlatch
*2
0C031H: Channel 1 warning 3 unlatch
*2
0C0FH: Channel 1 all warnings unlatch
*2
0C10H: Channel 2 warning 1 unlatch
*2
0C11H: Channel 2 warning 2 unlatch
*2
0C13H: Channel 2 warning 3 unlatch
*2
0C1FH: Channel 2 all warnings unlatch
*2
0CF0H: All channels warning 1 unlatch
*2
0CF1H: All channels warning 2 unlatch
*2
0CF2H: All channels warning 3 unlatch
*2
0CFFH: All channels all warnings unlatch
*2
Bit - 76543210
Overcurrent
Current hold
Input error
Blank
Blank