13.2 Temperature Controller/Servo/Inverter Connection 13-53
V680
(Default: OFF (all))
Available Device Memory
The available setting range of device memory varies depending on the model. Be sure to set within the range available for the
model to be used. Use [TYPE] when assigning indirect device memory for macro programs.
Indirect Device Memory Designation
Switch Setting Setting
SW1
SW2
Controller No.
setting
0
to 31 (32 to 99: not available)
SW3-1 Switch selection OFF: DIP switch enabled
SW3-3
SW3-4
Baud rate setting
SW3-5 Data length setting
OFF: 7 bits
ON: 8 bits
SW3-6
SW3-7
Parity
SW3-8 Stop bit
OFF: 2 bits
ON: 1 bit
SW3-9
Communication
protocol
OFF: 1 : 1
ON: 1 : N
SW3-10 Command system ON: V600 command format
SW1
SW2
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
Higher-order digit: 0 to 3
Lower-order digit: 0 to 9
SW3-3 SW3-4 Baud Rate
OFF OFF 9600
OFF ON 19200
ON OFF 38400
ON ON 115200
SW3-6 SW3-7 Parity
OFF OFF Even
OFF ON None
ON OFF Odd
ON ON Even
Device Memory TYPE Remarks
-- Setting area 0 00H
15 8 7 0
n + 0 Model (91 to 98) Device type
n + 1 Address No.
n + 2 Channel No. Bit designation
n + 3 00 Station number