13.2 Temperature Controller/Servo/Inverter Connection 13-59
13.2.14KM100
Communication Setting
Editor
Communication setting
(Underlined setting: default)
Temperature Controller
Communication level
Move to the communication setting level by using the key on the operation panel and make the required settings.
When the [LEVEL] key is held down for three seconds or longer in the run level, the setting level is selected.
When the [LEVEL] key is pressed in the setting level, the communication setting level is selected.
When the [LEVEL] key is held down for one second or longer, the run level is selected again.
(Underlined setting: default)
Available Device Memory
The available setting range of device memory varies depending on the model. Be sure to set within the range available for the
model to be used. Use [TYPE] when assigning indirect device memory for macro programs.
Indirect Device Memory Designation
For bit designation, an expansion code setting is required.
00H: when designating bit 0 to 15
01H: when designating bit 16 to 31
Item Setting Remarks
Connection Mode
1:1 / 1:n
/ Multi-link2 / Multi-link2 (Ethernet) /
1:n Multi-link2 (Ethernet)
Signal Level RS-232C / RS-422/485
Baud Rate 4800 / 9600 / 19200 / 38400 bps
Data Length 7
/ 8 bits
Stop Bit 1 / 2
bits
Parity None / Odd / Even
Targe t Port No. 0 to 99
Item Setting Remarks
Communication unit No. U-no 00 to 99
Baud rate bPS 4800 / 9600
/ 19200 / 38400
Data length LEn 7
/ 8
Stop bit Sbit 1 / 2
Parity Prty None / Even / Odd
Device Memory TYPE Remarks
C0 Variable area (instantaneous value) 00H Double-word, read only
C1 Variable area (average value) 01H Double-word, read only
C2 Variable area (maximum value) 02H Double-word, read only
C000 Parameter area 04H Double-word
15 8 7 0
n + 0 Model (91 to 98) Device type
n + 1 Address No.
n + 2 Expansion code Bit designation
n + 3 00 Station number