13-60 13. OMRON
PLC_CTL
Macro command “PLC_CTL F0 F1 F2”
Return data: Data stored from temperature controller to V series
*1 8000 (HEX): broadcasting
Contents F0 F1 (= $u n) F2
Status read out
1 - 8
(PLC1 - 8)
nStation number
2
n + 1 Command: 06H
n + 2 Operation status
Operation instructions
1 - 8
(PLC1 - 8)
n
Station number
*1
3
n + 1 Command: 30H
n + 2
0000H: Start calculation of arbitrary integral power consumption
0100H: Stop calculation of arbitrary integral power consumption
0200H: Arbitrary integral power consumption zero reset
0300H: Integral power consumption zero reset
0700H: Move to setting level
Log data read out
1000H:
Moving the read pointer to the top of the stored data
1001H:
Reading the log data at the read pointer
(The pointer advances.)
1002H:
Reading the log data at the read pointer and delete the read data
and earlier data from the memory
(The pointer advances.)
1100H: Delete all log data
9900H: Software reset