16-8 16. RKC
16.1.6 MA900 / MA901 (MODBUS RTU)
Communication Setting
Editor
Communication setting
(Underlined setting: default)
MA900/MA901
Setup setting mode
When the [R/S] key is pressed while the [SET] key is held down in the PV/SV monitor mode, the controller enters in the “setup
setting” mode.
(Underlined setting: default)
Available Device Memory
The available setting range of device memory varies depending on the controller model. Be sure to set within the range
available for the controller to be used. Use [TYPE] when assigning indirect device memory for macro programs.
Item Setting Remarks
Connection Mode
1:1 / 1:n
/ Multi-link2 /
Multi-link2 (Ethernet) /
1:n Multi-link2 (Ethernet)
Signal Level RS-232C / RS-422/485
Baud Rate 4800 / 9600 / 19200 bps
Data Length 8
bits
Stop Bit 1
bit
Parity None
/ Odd / Even
Target Port No. 1 to 31
Indication Item Setting Remarks
Add Slave address 1 to 31 Communication is not performed when “0” is set.
bPS Baud rate
1: 4800 bps
2: 9600 bps
3: 19200 bps
bIT Data configuration
0: 8 bits / 1 bit / none
2: 8 bits / 1 bit / even
4: 8 bits / 1 bit / odd
InT Interval time setting 0 to 250 msec
Device Memory TYPE Remarks
--- 00H