39
6-1-16 Frequency range of HE mode
Figure 6-17 Frequency range of HE mode
It changes into the “Frequency range of HE mode” display in pushing the
SET button. Push、▲ button/▼ button when you change the content
display. The content is changed when the SET button is pushed by the
content that changes and it moves to the next item display. Push the ESC
button when it returns to the “Frequency range of HE mode” item.
・When a utility input deviates from this setting range
HE mode : UPS transfer to On-Battery with output cut of moment.
Intelligent mode : UPS transfers to On-Battery with output cut of moment.
And if possible On-Line , UPS transfers to On-Line.
6-1-17 Language
Figure 6-18 Language
It changes into the “Language” display in pushing the SET button. Push、▲
button/▼ button when you change the content display. The content is
CONF I GURAT I ON
HE FREQ RANGE
HE FREQ RANGE
±1Hz
HE FREQ RANGE
±3Hz
HE FREQ RANGE
±5Hz
Factory
Setting
〆
CONF I GURAT I ON
LANGUAGE SELECT
LANGUAGE SELECT
ニホンコ゛/Japanese
LANGUAGE SELECT
エイコ ゛ / E n g l i s h
Factory
Setting
〆