11-3 ON Button Recovery
When UPS transfers to Converter OFF or On-Bypass by the alarm, UPS
does recovery operation to the alarm that recovery operation is possible by
pushing the ON button for three seconds. However, when the alarm is
detected again while recovery, recovery operation is stopped. Recovery
display is following.
Figure 11-2 Recovery Display
The alarm that can be recovered is the following alarm.
Output Over/Under Voltage
Output Offset
Input/Output Over Current
DC BUS Over Voltage
FAN Fault
Charger Fault
Short Circuit
Though the overload is not a breakdown, the recovery operation is
possible by pushing the ON button for three seconds.
・When 6-1-8 is invalidly set, this operation is not done.
This operation cannot be done while Manual Bypass. When operate, release the
manual Bypass
This operation is effective also for the alarm occured while OnBypass or
Converter off.
EBM1 REPOOFF 100
RE C OV E R Y  