63
LCD LED Buzzer Possible Cause Action
Lighting Continue
The UPS atmosphere
temperature exceeded
40℃.
Adjust the temperature
to 40 or less
Lighting Continue
The UPS atmosphere
temperature exceeded
41℃.
It returns automatically
when the
temperature falls on
40℃ or less.
Lighting Continue
The load has exceeded
102% Load.
Lighting Continue
The load has exceeded
110% Load.
Lighting Continue
The load has exceeded
130% Load.
Lighting Continue
The load has exceeded
150% Load.
Remove some equipment
from UPS.
Unlighting No
The condition of the self
test is not satisfactory.
The event was
generated while testing
self.
The alarm deletes after
one hour from occurd.
Lighting Continue
alarm
Remove equipment
from UPS.
Even retrying , if occur,
It
is necessary to repair
UPS. Contact your
service.
Lighting Continue
alarm
It is necessary to repair
UPS. Contact your
service.
OUT PUT OVE RCU RRT
OUTPUT OF FSET
SHORT CI RCUI T 
OUTP UT OVE RVOL T
OUTPUT UND ERVOL T
 DCBUS OVE RVOLT
DCBU S UND ERVOLT
UP S F AUL T
OVE R HEAT
INPUT OVERCURRT
CHAR GER F AUL T
AB F R L Y F AU LT
FAN FAULT
SOFT S TART F AUL T
TEMP FAUL T #1
TEMP FAUL T #2
OVER LOAD
 OVER L OAD # 1
 OVER L OAD # 2
 OVER L OAD # 3
BAT TER Y T EST NG