– 19 –
Dual Set Value Alarm Codes
Timer Code
(Note1) Available only for DO2
* Other than the alarm setting, each of the event output functions can be assigned to
DO1 to 5.
For more details on each of the event output functions, refer to “7-12. Digital output” - “1. DO
event setting” (page 14).
12
Model Specifications
12-1
PXG5/9 Standard Model List
Note 1: For outer dimensions of 48 x 96, the transmitter power supply output cannot be specified.
(5 in the fourth digit and T in the sixth digit cannot be specified.)
Note 2: If output 1 was for current or voltage output, option cannot be assigned to CT1 nor CT2.
(If 7th digit was assigned to G or J, or 11th digit to A, 5th digit cannot be assigned to E nor P.)
Note 3: RSV1 in option 1 and RSV2 in option 2 cannot be assigned simultaneously.
(If 7th digit was assigned to H or K, 11th digit cannot be assigned to D.)
Note 4: In case, in option 1, of DI 2 points + RSV1 or RS485 + DI 1 + RSV1, output 2 cannot be
assigned.
(If 7th digit was assigned to F or 2, 6th digit cannot be assigned to A, C, E, P, R nor S.)
Note 5: In case of CT1 in option 1, or CT2 in option 2, digit output cannot be assigned to None.
(If 7th digit was assigned to G or J, or 11th digit to A, 9th digit cannot be assigned to 0.)
Note 6: CT1 in option 1 and CT2 in option 2 cannot be assigned simultaneously.
(If 7th digit was assigned to G or J, 11th digit cannot be assigned to A.)
Type DO1 to DO5 Alarm Type Action diagram
High/Low limit
alarm
16 High/Low absolute alarm
17 High/Low deviation alarm
18 High absolute/Low
deviation alarm
19 High deviation/Low
absolute alarm
20 High/Low absolute alarm
(with hold)
21 High/Low deviation alarm
(with hold)
22 High absolute/Low
deviation alarm (with hold)
23 High deviation/Low
absolute alarm (with hold)
Zone alarm 24 High/Low absolute alarm
25 High/Low deviation alarm
26 High absolute/Low
deviation alarm
27 High deviation/Low
absolute alarm
28 High/Low absolute alarm
(with hold)
29 High/Low deviation alarm
(with hold)
30 High absolute/Low
deviation alarm (with hold)
31 High deviation/Low
absolute alarm (with hold)
Type DO1 to DO5 Alarm Type Action diagram
Timer 32 ON delay timer
33 OFF delay timer
34 ON/OFF delay timer
Point
What is alarm with hold?
The alarm will not turn ON immediately when the process value gets into
the alarm band and enters again. If without hold, alarm may turn ON when
starting up.
Caution
When alarm action code is changed, alarm set value may also become dif-
ferent from previous settings.
When alarm action type code is changed, turn off the power once, and
then re-start the controller, before starting control.
Aln: AL1 to AL5 show the alarm set values
ALnh: AL1h to AL5h show the alarm set values
ALnL: AL1L to AL5L show the alarm set values
dLYn: dLY1 to dLY5 show the alarm delay on set values
PV
t
ALnh
ALnL
SV
PV
t
ALnh
ALnL
SV
PV
t
ALnh
ALnL
SV
PV
t
ALnh
ALnL
PV
t
ALnL
ALnL
SV
PV
t
ALnh
ALnL
SV
PV
t
ALnh
ALnL
SV
PV
t
ALnh
ALnL
PV
t
ALnh
ALnL
SV
PV
t
ALnh
ALnL
SV
PV
t
ALnL
ALnh
SV
PV
t
ALnL
ALnh
PV
t
ALnh
ALnL
SV
PV
t
ALnh
ALnL
SV
PV
t
ALnL
ALnh
SV
PV
t
ALnL
ALnh
DI
ALM
dLYn
DI
ALM
dLYn
DI
ALM
dLYn
dLYn
PV (process value)
power on
lower limit alarm
lower limit alarm
(with hold)
power on
power off
Lower limit alarm
output area
off off off
on on
off off
on
Digit
Specifications 1 2 3 4 5 6 7 8 - 9
10 11 12 13
-
14
Notes
4 <Size of front WxH>
48 x 96 mm P X G 5
Note 1
96 x 96 mm P X G 9
5 <Output 1>
Relay contacts A
SSR drive C
Current (0 to 20mA DC / 4 to 20mA DC)
E
Note 2
Voltage (0 to 5V DC / 1 to 5V DC /
0 to 10V DC / 2 to 10V DC)
P
Note 2
6 <Output 2>
None Y
Relay contacts A
Note 4
SSR drive C
Note 4
Current (0 to 20mA DC / 4 to 20mA DC)
E
Note 4
Voltage (0 to 5V DC / 1 to 5V DC /
0 to 10V DC / 2 to 10V DC)
P
Note 4
Re-transmission output current
(0 to 20mA DC/ 4 to 20mA DC)
R
Note 4
Re-transmission output voltage
(0 to 5V DC / 1 to 5V DC /
0 to 10V DC / 2 to 10V DC)
S
Note 4
Transmitter power supply T
Note 1,4
7 <Option 1>
None Y
RS 485 M
Digital input (No. 1) + digital input
(No. 2)
T
Digital input (No. 1) + RSV1 H
Note 3
Digital input (No. 1) + CT1 G
Note
2,5,6
RS 485 + digital input (No. 1) V
RS 485 + RSV1 K
Note 3
RS 485 + CT1 J
Note
2,5,6
RS 485 + digital input (No. 1)+RSV1
F
Note 4
Digital input (No. 1) + RSV1
+Digital input (No. 2)
2
Note 4
8 <Revision symbols> 1
9 <Digital Output>
(Relay contact output)
None 0
Note 5
Digital output 1 point (No.1) 1
Digital output 2 points (No.1, 2) F
Digital output 3 points (No.1, 2, 3) M
Digital output 2 points
[independent common] (No.1, 2)
J
10
<Power Supply> <Instruction Manual>
100V/240V AC no instruction
manual
N
100V/240V AC English instruction
manual
V
24V AC/DC no instruction manual C
24V AC/DC English instruction
manual
B
11 <Option 2>
None Y
Digital input (No. 3, 4, 5) + CT2 A
Note
2,5,6
Digital input (No. 3, 4, 5) B
Digital input (No. 3, 4, 5)
+ digital outputs
(No. 4, 5) [transistor output]
C
Digital input (No. 3, 4, 5) + RSV2 D
Note 3
12 0
13 0

Table of Contents