Parameter Range Description Default DSP
settings settings
ProG oFF/rUn/HLd Ramp/soak command oFF dSP1-1
P 0.0 - 999.9%FS Proportional band 5.0 dSP1-2
I 0 - 3200sec Integral time 240 dSP1-4
D 0.0 - 999.9sec Derivative time 60 dSP1-8
AL 0 - 100%FS Low Alarm Setpoint 10 dSP1-16
AH 0 - 100%FS High Alarm Setpoint 10 dSP1-32
TC 1 - 150sec Cycle Time (output #1) dSP1-64
HYS 0 - 50%FS Hysteresis 1 dSP1-128
Hb 0.0 - 50.0A Heater-break alarm S.P. 0.0 dSP2-1
AT 0 - 2 Auto-tuning command 0 dSP2-2
TC2 1 - 150sec Cycle Time (output #2) dSP2-4
CooL 0.0 - 100.0 Proportional band 1.0 dSP2-8
coefficient for cooling
db -50.0 - 50.0% FS Deadband/Overlap 0.0 dSP2-16
PLC1 - N/A -3.0 dSP2-32
PHC1 - N/A 103.0 dSP2-64
PCUT - N/A 0 dSP2-128
bAL 0 - 100% Balance 0.0/50.0 dSP3-1
Ar 0 - 100%FS Anti-reset windup 100%FS dSP3-2
LoC 0 - 2 Lock out 0 dSP3-4
STAT -- Ramp/soak status oFF dSP3-8
SV-1 0 - 100%FS 1st S.P. 0%FS dSP3-16
TM1r 0 - 99hr 59min 1st ramping time 0.00 dSP3-32
TM1S 0 - 99hr 59min 1st soaking time 0.00 dSP3-64
SV-2 0 - 100%FS 2nd S.P. 0%FS dSP3-128
TM2r 0 - 99hr 59min 2nd ramping time 0.00 dSP4-1
TM2S 0 - 99hr 59min 2nd soaking time 0.00 dSP4-2
SV-3 0 - 100%FS 3rd S.P. 0%FS dSP4-4
TM3r 0 - 99hr 59min 3rd ramping time 0.00 dSP4-8
TM3S 0 - 99hr 59min 3rd soaking time 0.00 dSP4-16
SV-4 0 - 100%FS 4th S.P. 0%FS dSP4-32
TM4r 0 - 99hr 59min 4th ramping time 0.00 dSP4-64
TM4S 0 - 99hr 59min 4th soaking time 0.00 dSP4-128
MOD 0 -15 Ramp/Soak Mode code 0 dSP5-1
22
PXZ QUICK REFERENCE
Primary Menu
Parameter Range Description Default DSP
settings settings
P-n1 0 -19 Control Action code dSP5-4
P-n2 0 - 16 Input type code dSP5-8
P-dF 0.0 - 900.0sec Input filter constant 5.0 dSP5-16
P-SL -1999 - 9999 Lower range of input 0%FS dSP5-32
P-SU -1999 - 9999 Upper range of input 100%FS dSP5-64
P-AL 0 - 15 Alarm Type 2 code 9 dSP5-128
P-AH 0 - 11 Alarm Type 1 code 5 dSP6-1
P-An 0 - 50%FS Alarm Hysteresis 1 dSP6-2
P-dP 0 - 2 Decimal point position 0 dSP6-4
rCJ - - ON dSP6-8
PVOF -10 - 10%FS PV offset 0 dSP6-16
SVOF -50 - 50%FS SV offset 0 dSP6-32
P-F °C/°F °C/°F Selection dSP6-64
PLC2 - N/A -3.0 dSP6-128
PHC2 - N/A 103.0 dSP7-1
FUZY OFF/ON Fuzzy control OFF dSP7-2
GAIN - N/A 1 dSP7-4
ADJO - Zero calibration 0 dSP7-8
ADJS - Span calibration 0 dSP7-16
OUT - N/A -3.0 dSP7-32
dSP1-7 0-255 Parameter mask -
† Based on the model
PXZ QUICK REFERENCE
Secondary Menu