18
[Table 4] Control action codes
Parameter:
[Burn-out direction]
Output direction if input is outside range or has an error.
Lower limit: OFF or 4mA or less
Upper limit: ON or 20mA or more
[Caution for dual output form]
(option)
(1) ID operation can not be set separately for heating/cooling.
(2) Setting the heating side to two position operation will set the cooling side to the same operation.
(3) If set to CooL=0.0, cooling side takes ON/OFF operation.
In this case, ON/OFF operation hysteresis is fixed (0.5%FS).
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
Single
Dual
Output 1
Reverse action
Direct action
Reverse action
Direct action
Reverse action
Direct action
Output 2
---
Direct action
Reverse action
Output 1
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Output 2
---
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Control action
Burn-out direction
Code
(P-n1)
Output type