2-3 Parameter functions and setting method
Setting of set value (SV)
[Description]
Set values are control target values.
Upper/lower limit of set value is des-
ignated by No. 2 block parameter
P-SU/P-SL. P-SL (lower limit) or
P-SU (upper limit) cannot be used
for setting outside the range (See
page 29).
When a temperature sensor is used
for input, the unit of set value is °C
or °F. Selection between °C and °F
is made by No. 2 block parameter
P-F.
Related parameter: P-SL (Page 29)
P-SU (Page 29)
LOC (Page 22)
Example) Altering SV 250°C to 1195°C
SEL
ENT
SV
DATA
Key operation Description
Press the SEL key to display P.
Press DATA key once, then SV
display lamp is lighted, and current
value is displayed.
Press the or key to display
1195.
SV is automatically registered in 3
seconds.
Press the SV key to return to the
operating status display.
Also, after 30 seconds without key
operation, data is automatically
returned to the operating status
display.
Display
PV
SV