34
Example) Set the zero shift width of 5°C to input value
1200°C
Key operation Description
Press the SEL key for 3 seconds,
and P-n1 is displayed.
Press the SEL key repeatedly until
PVOF is displayed.
Press the or key to display
5.
Press the DATA key. Data is
displayed.
Press the SV key when you need to
display the operation status display.
After pressing the ENT key, the data
is registered.
Display
SEL
SEL
SV
DATA
ENT
PV offset (Setting range: -10 to 10%FS)
[Description]
• Set value is added to designated in-
put value. It is mainly used when
recorder needs to conform with the
designated value.
• Control is performed by the dis-
played PV value (PV offset is
added).