6. Capacity compensation rate for pipe length and height
difference
Height difference H
Indoor unit is higher than outdoor unit
*
1
Indoor unit is lower than outdoor unit *
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HH
6-1. Models: ROG07KMTA and ROG09KMTA
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 15 20
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15 0.872 0.910
10 0.961 0.886 0.925
7.5 0.979 0.965 0.890 0.929
5 0.992 0.983 0.969 0.893 0.933
0 1.000 0.991 0.976 0.901 0.940
Indoor unit is lower than
outdoor unit *2
-5 1.000 0.991 0.976 0.901 0.940
-7.5 0.991 0.976 0.901 0.940
-10 0.976 0.901 0.940
-15 0.901 0.940
HEATING
Pipe length (m)
5 7.5 10 15 20
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15 0.832 0.822
10 0.917 0.832 0.822
7.5 0.961 0.917 0.832 0.822
5 1.000 0.961 0.917 0.832 0.822
0 1.000 0.961 0.917 0.832 0.822
Indoor unit is lower than
outdoor unit *2
-5 0.955 0.956 0.912 0.828 0.818
-7.5 0.954 0.910 0.826 0.816
-10 0.908 0.824 0.814
-15 0.815 0.805
- 49 -
OUTDOOR UNIT
ROG07-14KMTA