3-10
Section 3 System Denition
3-3-4 Remote RUN/STOP bit setting
You can designate an arbitrary external input (only one bit) for the “Start/Stop input” to the main unit.
If this parameter is set, start/stop, download and clear operations from loader take effect only when the “RUN/STOP bit” is set ON.
Notes:
The input that is designated for the “remote RUN/STOP input” must be assigned to the default task by I/O group setting.
* No “remote RUN/STOP bit” is set by default. This setting is disabled when a fatal fault occurs.
<Setting procedure>
Click the [Remote RUN/STOP setting] tab on the “Main unit parameter” dialog box to display the following window.
Click the button for the bit to designate for the “remote RUN/STOP input,” and then click the [OK] button.