1-12
Section 1 Specications
(2) Resource operating status %MW10.0 (Read only)
This area indicates the resource (main unit) operating status and operating modes.
Address Name Description
%MX10.0.0 Run ON while the main unit is running.
%MX10.0.1 Stop ON while the main unit is stopped.
%MX10.0.2 Fatal fault ON when a fatal error occurs in the main unit.
%MX10.0.3 Nonfatal fault ON when a nonfatal error occurs in the main unit.
%MX10.0.4
|
%MX10.0.8
Not used
%MX10.0.9 Automatic operation mode ON while in the automatic operation mode.
%MX10.0.10 Not used
%MX10.0.11 Battery-less operation mode ON while in the battery-less operation mode.
%MX10.0.12
|
%MX10.0.15
Not used
Address Name Description
%MX10.1.0
|
%MX10.1.5
Not used
%MX10.1.6 User ROM card connection state
ON: Connected
OFF: Not connected
%MX10.1.7 User ROM card write protect
ON: Write-protected
OFF: Write-permitted (enabled when “%MX10.1.6” is ON)
%MX10.1.8 STOP position ON if the set bit is OFF (STOP) when using the remote RUN/STOP function
%MX10.1.9 Not used
%MX10.1.10 TERM position ON when the remote RUN/STOP function is not used
%MX10.1.11
|
%MX10.1.15
Not used
Automatic operation mode
In this mode, the main unit starts operation when the power switch is turned ON. SPF is always set in this mode.
Battery-less operation mode
In this mode, all memories are initialized (assigned initial values or cleared to zero) when the power of the main unit is turned
ON. The battery voltage is not checked. You can enable or disable this mode in the “CPU running denition” on the “Main unit
parameter” dialog box.
(3) Resource switch / User ROM state %MW10.1 (Read only)