1. Specifications
1-1. Indoor unit
Type
Ceiling
Inverter heat pump
Model name ABHG54KRTA
Power supply 3N 400 V ~ 50 Hz
Power supply intake Outdoor unit
Available voltage range 342—457 V
Capacity
Cooling
Rated
kW 13.4
Btu/h 45,700
Min.—Max.
kW 4.5—14.5
Btu/h 15,350—49,400
Heating
Rated
kW 15.5
Btu/h 52,900
Min.—Max.
kW 4.7—16.5
Btu/h 16,040—56,310
Input power
Cooling
Rated
kW
4.45
Max. 5.23
Heating
Rated 4.43
Max. 4.83
Current
Cooling
Rated A
8.0
Heating 8.0
EER Cooling
kW/kW
3.01
COP Heating 3.50
Power factor
Cooling
%
80.5
Heating 80.4
Moisture removal L/h (pints/h) 5.0 (8.8)
Maximum operating current *
1
Cooling
A
14.0
Heating 14.0
Fan
Airflow rate
Cooling
HIGH
m
3
/h
2,100
MED 1,700
LOW 1,500
QUIET 1,220
Heating
HIGH 2,100
MED 1,700
LOW 1,500
QUIET 1,220
Type × Q'ty Sirocco × 4
Motor output W 130
Sound pressure level *
2
Cooling
HIGH
dB (A)
48
MED 44
LOW 41
QUIET 38
Heating
HIGH 48
MED 44
LOW 41
QUIET 38
Heat exchanger type
Dimensions (H × W × D) mm 294 × 1,335 × 39.9
Fin pitch mm 1.30
Rows × Stages 3 × 14
Pipe type Copper
Fin type Aluminum
Enclosure
Material Steel sheet
Color
White
Approximate color of Munsell N9.25/
Dimensions
(H × W × D)
Net
mm
235 × 1,700 × 705
Gross 330 × 1,785 × 825
Weight
Net
kg
38
Gross 48
Connection pipe
Size
Liquid
mm (in)
Ø9.52 (Ø3/8)
Gas Ø15.88 (Ø5/8)
Method Flare
Drain hose
Material PVC
Tip diameter mm Ø25 (I.D.), Ø32 (O.D.)
Operation range
Cooling
°C 18 to 32
%RH 80 or less
Heating °C 16 to 30
Remote controller (Option)
Wired remote controller, Wireless remote controller, Mobile app*3 (FGLair
™
)
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Maximum current is maximum value when operated within the operation range.
• *2: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
• *3: Available on Google Play
™
store or on App Store
®
. Optional WLAN adapter is also required. For details, refer to the setting manual.
1-1. Indoor unit
- (01-1) - 1. Specifications
GENERAL
INFORMATION
GENERAL
INFORMATION