EasyManua.ls Logo

Fujitsu ABYG54KRTA - High Pressure Protection; Low Outdoor Temperature Protection

Fujitsu ABYG54KRTA
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8-6. High pressure protection
Trigger condition
Pressure switch: Off (Open: Higher than 4.2 MPa)
Compressor stop
Release condition
Pressure switch: On (Close: Lower than 3.2 MPa)
(3 minutes after compressor stop)
Compressor restart
8-7. Low outdoor temperature protection
When the outdoor temperature sensor detects lower than the trigger condition below, the compres-
sor is stopped.
Operation mode Cooling/Dry
Trigger condition -20°C
Release condition -15°C
8-6. High pressure protection - (04-28) - 8. Various protections
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS

Table of Contents

Related product manuals