En-4
Wall height condition Necessary installation space
When H1 is 1500 (mm) or less L1 500 (mm)
When H1 is 1500 (mm) or more L1 500+h1÷2 (mm)
When H2 is 500 (mm) or less L2 100 (mm)
When H2 is 500 (mm) or more L2 100+h2÷2 (mm)
<Side view>
<Front> <Rear>
Wall
Wall
Fig. 1
Fig. 2 Single installation
30mm
or more
10mm
or more
<Top view>
<Front>
<Rear>
Fig. 3 Multiple installations
<Top view>
30mm or
more
20mm or
more
10mm or
more
<Front>
<Rear>
20mm or
more
(2) Concentrated installation
Provide installation spaces L3, L4, and L5 in accordance with the table below ac-
cording to the wall height (front side, rear side) conditions.
• Provide installation spaces other than L3, L4, and L5 in accordance with the condi-
tions shown in the gure below.
Ventilation resistance can be ignorable when the distance from a wall or product,
etc. is larger than 2m.
Wall height condition Necessary installation space
When H3 is 1500 (mm) or less L3 500 (mm)
When H3 is 1500 (mm) or more L3 500+h3÷2 (mm)
When H4 is 500 (mm) or less L4 200 (mm)
When H4 is 500 (mm) or more L4 200+h4÷2 (mm)
When H5 is 500 (mm) or less L5 200 (mm)
When H5 is 500 (mm) or more L5 200+h5÷2 (mm)
Fig. 4
h3
1500
L3
L4
500
h4
H3
H4
<Side view>
<Front>
<Rear>
Wall
Wall
Fig. 5
L5
L5
500
h5
500
h5
H5
H5
<Front view>
Wall Wall
Fig. 6
<Top view>
800mm
or more
800mm
or more
20mm or
more
20mm or
more
L4
L3
L5L5
Fig. 7
<Top view>
500mm
or more
1000mm
or more
20mm or
more
20mm or
more
L4
L3
L5
L5
3. 3. 2. When install near unlimited height wall
(1) Single and multiple installations
There are no restrictions on the height of the wall.
The wall (without height restrictions) must not exist on the both sides (left / right)
of outdoor unit. Also, must not exist on the both sides (front / rear) of outdoor
unit.
• Provide installation spaces other than L6 in accordance with the conditions
shown in the gure below.
Ventilation resistance can be ignorable when the distance from a wall or prod-
uct, etc. is larger than 2 m.
When installing with the REAR of the outdoor unit facing the wall side
Condition Necessary installation space
When B 400 (mm) L6 200 (mm)
When 20 B < 400 (mm) L6 200 + (400-B) ×3 (mm)
Fig. 8 Single installation
<Top view>
<Front>
<Rear>
200mm
or more
100mm
or more
Fig. 9 Multiple installations
<Top view>
<Front>
<Rear>
200mm
or more
B
L6
B
9378945180-02_IM.indb 49378945180-02_IM.indb 4 2014/11/10 19:39:552014/11/10 19:39:55