EasyManua.ls Logo

Fujitsu Airstage AJT040LCLAH - External Input and External Output

Fujitsu Airstage AJT040LCLAH
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
En-12
Be sure to use one side of a twisted-pair cable when using transmission cable with 2 sets
of twisted-pair cables.
Wind with insulation tape to prevent short circuit
Use one side of the
twisted-pair cable
Connect both ends of shielded wire to earth.
6. 6. External input and external output
6. 6. 1. Terminal position
Base heater
(CN115:Black)
Outdoor unit
PC board
Input 4
(CN134:Red)
Input 3
(CN133:White)
Input 2
(CN132:Green)
Input 1
(CN131:Yellow)
BASE HEATER
CN115 (BLK)
Input 5
(CN135 :
Orange)
PULSE
IN
CN134
CN133
CN132
CN135
CN136
CN137
CN131
EXT.
OUT. 1
EXT.
IN. 4
EXT.
IN. 3
EXT.
IN. 2
EXT.
IN. 1
EXT.
OUT. 2
(ORG)
(RED)
(WHT)
(GRN)
(YEL)
(BLK)
(BLU)
Output 1
(CN136 :
Black)
Output 2
(CN137:
Blue)
CAUTION
Do not bundle the cable for base heater with other cables.
When connecting cable to Input2
Cable (for external input and output)
Cable tie (tightened with transmission cable)
Cable (for external input and output)
* If the outdoor unit is not installed in the wall, cover the exposed part of cable
with a 1 mm thick or more insulation tubing.
6. 6. 2. External input terminal
Setting to low noise mode, cooling priority/heating priority selection, outdoor unit
operation peak control setting, emergency/batch stop and electricity meter pulse are
possible from the outside.
Wiring method and speci cations
* A twisted pair cable (0.33mm
2
(22AWG)) should be used. Maximum length of cable is
150m.
* Use an external input and output cable with appropriate external dimension, depend-
ing on the number of cables to be installed
* For each input, pin No.1 is of positive polarity and pin No.2 is of ground level.
connected unit
connected unit
connected unit connected unit connected unit
Input1
CN131
(Yellow)
Input2
CN132
(Green)
Input3
CN133
(White)
Input4
CN134
(Red)
Input5
CN135
(Orange)
P. C .B
Operation behavior
Each input terminal works as follows.
Connector Input signal Status
Input1
CN131 (Yellow)
OFF Normal operation
ON Low noise mode operation
Input2
CN132 (Green) *1
OFF Cooling priority
ON Heating priority
Input3
CN133 (White)
OFF Normal operation
ON Outdoor unit operation peak control
Input4
CN134 (Red)
OFF Normal operation
ON Batch stop or Emergency stop operation *2, *3
Input5
CN135 (Orange) *4
No pulse No information from electricity meter
Pulse Power usage information from electricity meter
The operations of each input terminal and the selection of function are set with the push button
on the PC board of outdoor unit. About the setting, please refer to “7.4. Push button setting”.
NOTE:
*1:
The “external input priority mode” must be set by pressing push button on PC
board of outdoor unit. (Refer to “7. FIELD SETTING”.)
*2:
Batch stop or Emergency stop pattern can be selected by outdoor unit PC board
push button. (Refer to “7. FIELD SETTING”.)
*3:
The emergency stop function mounted in the J-II does not guarantee the regulations
of each country. For this reason, su cient checking is necessary regarding use.
Especially, since the fact that the equipment may not be emergency-stopped in the
case of breaking of the wiring to the external input terminals and communication
line, communication error due to noise, VRF external input circuit trouble, etc. must
be considered, the provision of double measures that add direct interruption of the
power supply by switch, etc. is recommended as a precaution.
*4:
Pulse input to CN135 must be width 50ms or more, and must be interval 50ms or more.
6. 6. 3. External output terminal
You can detect the operation condition of outdoor unit and the abnormal situation of
both indoor and outdoor unit.
Wiring method and speci cations
Error status
This output indicates the outdoor unit and connected indoor unit's “Normal” or “Error”
status.
Operation status
This output indicates the outdoor unit's “Operation” status.
Connector Output voltage Status
Output1
CN136 (Black)
0V Normal
DC 12-24 V *5 Error
Output2
CN137 (Blue)
0V Stop
DC 12-24 V *5 Operation
9380545149-02_IM_EN.indd 129380545149-02_IM_EN.indd 12 9/7/2021 1:38:54 PM9/7/2021 1:38:54 PM

Related product manuals