En-13
+
+-
P. C .B
*7
*5
*6
1
2
CN136
(Black)
or CN137
(Blue)
DC power supply
(External) 12 - 24V
Connected load
(Operation Indicator
or Error Indicator)
connected unit
*5: Provide a DC12 to 24V power supply.
Select a power supply capacity with an ample surplus for the connected load.
*6: The allowable current is 30mA or less.
Provide a load resistance such that the current becomes 30mA or less.
*7: Polarity is [+] for pin 1 and [-] for pin 2. Connect correctly.
Do not impress a voltage exceeding 24V across pins 1-2.
* A twisted pair cable (0.33mm
2
(22AWG)) should be used. Maximum length of cable is 150m.
* Use an external input and output cable with appropriate external dimension, depend-
ing on the number of cables to be installed.
6. 6. 4. Base heater terminal
This is the output signal for base heater. Output signal ON, when the outdoor tempera-
ture goes down below 2°C, and signal OFF at the outdoor temperature 4°C.
1
2
3
4
Voltage: power supply
input voltage
cable
(0.82mm
2
(18AWG))
P. C .B .
Base heater *9
CN115
(Black)
*8
* 8: Connect to pin 1 and pin 3. No connection pin2 and pin4.
* 9: The allowable current is 1A or less.
7. FIELD SETTING
CAUTION
Discharge the static electricity from your body before setting up the DIP switches.
Never touch the terminals or the patterns on the parts that are mounted on the PC
board.
7. 1. Field setting switches
Remove the service panel of the outdoor unit and the cover of the electrical component
box to access the PC board of the outdoor unit.
PC board switches for various settings and LED displays are shown in the gure.
7. 2. DIP switch setting
7. 2. 1. List of Settings
SET5 must be set for the DIP switch.
Con gure the settings before turning on the power. Settings for SET1, SET2, SET3 and
SET4 DIP switches are factory
setting
ones. Do not change them.
DIP Switch Function
SET1 1-4 Forbidden
SET2 1-4 Forbidden
SET3 1-4 Forbidden
SET4 1-4 Forbidden
SET5
1-3 Forbidden
4 Terminal resistor setting
X 10 X 1
SET5
7 Segment
display
Push button
LED lamp
POWER
LED105
LED104
REF AD
SET 1
SW101
SET 2
SW102
SET 3
SW103
SET 4
SW104
ERROR
MODE
LED101
(GREEN)
MODE
/EXIT
SELECT
ENTER
SW106
SW107
SW108
SW109
SW105
LED102
(RED)
Rotary switch
Outdoor unit printed circuit board
DIP switch
9380545149-02_IM_EN.indd 139380545149-02_IM_EN.indd 13 9/7/2021 1:38:54 PM9/7/2021 1:38:54 PM

Related product manuals