EasyManua.ls Logo

Fujitsu Airstage ARUH72TLAV1 - Remote Sensor (Optional Parts)

Fujitsu Airstage ARUH72TLAV1
16 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
En-11
When function setting is “Forced stop” mode.
[In the case of “Edge” input]
Connector Input signal Command
Ch1 of CNA01 or CNA02
OFF ON Forced stop
ON OFF Normal
[In the case of “Pulse” input]
Connector Input signal Command
CNA01 or CNA02
Ch1 OFF ON Forced stop
Ch2 OFF ON Normal
* When the forced stop is triggered, indoor unit stops and Operation/Stop operation by a
remote controller is restricted.
* When forced stop function is used with forming a remote controller group, connect the
same equipment to each indoor unit within the group.
• Selection method of functions
“Operation/Stop” mode or “Emergency stop” mode, “Forced stop” mode can be selected
with function setting of indoor unit.
Forced thermostat off function
[“Edge” input only]
Connector Input signal Command
Ch3 of CNA03 or CNA04
OFF ON Thermostat off
ON OFF Normal
(2) External output
A twisted pair cable (22AWG) should be used. Maximum length of cable is 82 ft. (25 m).
Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
Output voltage: Hi DC12V±2V, Lo 0V.
Permissible current: 50mA
Output select
When indicator etc. are connected directly
Indicator 1
Indicator 2
Indicator 3
Indicator 4
connected unit
P.C .B
CNB
01
When connecting with unit equipped with a power supply
CNB
01
P.C .B
Connected
device 1
Connected
device 2
Connected
device 3
Connected
device 4
Relay (locally purchased)
Operation behavior
*If function setting “60” is set to “00”
Connector Output voltage Status
CNB01
External output1
Pins 1-2
0V Stop
DC 12 V Operation
External output2
Pins 1-3
0V Normal
DC 12 V Error
External output3
Pins 1-4
0V Indoor unit fan stop
DC 12 V Indoor unit fan operation
External output4
Pins 1-5
0 V External heater OFF
DC 12V External heater ON
Indoor unit fan setting for external heater
Fan setting when turning ON output to the connected external heater can be set by
changing Dip switch on PC board.
Dip switch
[SET2 SW3]
Fan setting when
ON is output to the
external heater
Explanation
OFF
(Factory setting)
OFF
For the fan setting details, see the
Design & Technical Manual.
ON ON
(3) Connection methods
• Wire modi cation
Remove insulation from wire attached to wire kit connector.
Remove insulation from locally purchased cable. Use crimp type insulated butt connector
to join eld cable and wire kit wire.
Connect the wire with connecting wire with solder.
IMPORTANT:
Be sure to insulate the connection between the wires.
Option parts
External input/output wire
Solder and insulate the connected parts.
Locally purchased
Connection terminals and wiring arrangement
In following gure, all the possible connectors are connected for description.
In actual installation, you cannot connect all the connectors at once.
Cable clamp
Controller PCB
6.6. Remote sensor (Optional parts)
For the installation method, please refer to the INSTALLATION MANUAL of remote
sensor.
Connection methods
• Connection terminals
Remote sensor terminal
(CN8)
Controller PCB
9365748237_IM.indb Sec1:119365748237_IM.indb Sec1:11 6/16/2015 4:24:46 PM6/16/2015 4:24:46 PM

Related product manuals