En-12
• Wiring arrangement
Cable tie
(locally purchased)
Controller PCB
Remove the existing connector and replace it with the remote sensor connector (ensure
that the correct connector is used).
The original connector should be insulated to ensure that it does not come into contact
with other electrical circuitry.
Use conduit hole when external output cable is used.
Setting for room temperature correction
When a remote sensor is connected, set the function setting of indoor unit as indicated
below.
Function Number “30”:
Set the Setting Number to “00”. (Default)
Function Number “31”:
Set the Setting Number to “02”.
* Refer to “7.4. Function setting” for details about Function Number and Setting Number.
6.7. IR receiver unit (Optional parts)
For the installation method, please refer to the INSTALLATION MANUAL of IR receiver
unit.
Connection methods
• Connection terminals
IR receiver unit terminal
(CN18)
Controller PCB
• Wiring arrangement
Cable clamp
Core
Controller PCB
7. FIELD SETTING
There are 3 methods for address setting by FIELD SETTING as follows.
Set by either of the methods.
Each setting method is described (1) to (3) below.
(1)
IU AD, REF AD SW settings
.............. This section (7.1. Setting the address)
(2) Remote controller settings ............... Refer to the wired or wireless remote controller
manual for detailed setting information. (Set IU
AD, REF AD SW to 0)
(3) Automatic address settings ............. Refer to the outdoor unit manual for detailed
setting information. (Set IU AD, REF AD SW to 0)
CAUTION
Be sure to turn OFF the power before performing the eld setting.
7.1. Setting the address
Manual address setting method
If the receiver unit is attached, the indoor unit address and the refrigerant circuit
address can also be set up through the wireless remote controller.
CAUTION
Use an insulated screwdriver to set the DIP switches.
Rotary switch
Example: “0”
Rotary switch
Example: “0”
9365748237_IM.indb Sec1:129365748237_IM.indb Sec1:12 6/16/2015 4:24:46 PM6/16/2015 4:24:46 PM