Fujitsu Airstage ARUH72TLAV1 - Custom Code Setting; Static Pressure Mode

Fujitsu Airstage ARUH72TLAV1
16 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
En-13
Setting
Setting
range
Type of switch
Indoor unit address 0 to 63
Setting
example 2
IU AD × 10 IU AD × 1
Refrigerant
circuit
address
0 to 99
Setting
example 63
REF AD × 10
REF AD × 1
(1) Indoor unit address
Rotary switch (IU AD × 1)...Factory setting “0”
Rotary switch (IU AD × 10)...Factory setting “0”
When connecting multiple indoor units to 1 refrigerant system, set the address at IU
AD SW as shown in the Table A.
(2) Refrigerant circuit address
Rotary switch (REF AD × 1)...Factory setting “0”
Rotary switch (REF AD × 10)...Factory setting “0”
In the case of multiple refrigerant systems, set REF AD SW as shown in the Table A
for each refrigerant system.
Set to the same refrigerant circuit address as the outdoor unit.
If working in an environment where the wireless remote controller can be used, the
addresses can also be set using the remote controller.
If setting the addresses using the wireless remote controller, set the indoor unit
address and refrigerant circuit address to “00”.
(For information on setting using the wireless remote controller.)
Table A
Address
Rotary
switch
setting
Address
Rotary switch
setting
Refrigerant circuit
REF AD SW
Indoor unit
IU AD SW
× 10 × 1 × 10 × 1
000000
101101
202202
303303
404404
505505
606606
707707
808808
909909
10 1 0 10 1 0
11 1 1 11 1 1
12 1 2 12 1 2
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
99 9 9 63 6 3
Do not set the indoor unit address (IU AD SW) at 64 to 99.
It may result in failure.
(3) Remote controller address
i) 3-wire type
Rotary switch (RC AD SW)...Factory setting “0”
When connecting multiple indoor units to 1 standard wired remote controller, set the
address at RC AD SW in sequence from 0.
Setting Setting range Type of switch
Remote controller
address
0 to 15
Setting
example 0
RC AD
Example
If 4 indoor units are connected.
RC AD SW
0
RC AD SW
1
RC AD SW
2
RC AD SW
3
Indoor unit
Remote
controller
Indoor unit Indoor unit Indoor unit
RC AD SW
01234567
Address
01234567
RC AD SW
89ABCDEF
Address
8 9 10 11 12 13 14 15
ii) 2-wire type
Rotary switch (RC AD SW)...Factory setting “0”
Since the remote controller address settings are automatically con gured, you do not
need to con gure them.
If con guring manually, it is necessary to con gure both the indoor unit and the remote
controller.
For details, please refer to the remote controller manual.
7.2. Custom code setting
Selecting the custom code prevents the indoor unit mix-up.
(Up to 4 codes can be set.)
Perform the setting for both the indoor unit and the remote controller.
A B C D
A B C D
Indoor
unit
Remote
controller
Confusion
Code change
Custom code setting for indoor unit
Set the DIP switch SET 3 SW1, SW2 referring to the Table B.
ON
OFF
Dip switch “SET 3”
SW
1
SW
2
SW
3
SW
4
Table B
Custom code
A (Factory setting) B C D
DIP switch SET3 SW1 OFF ON OFF ON
DIP switch SET3 SW2 OFF OFF ON ON
7.3
. Static pressure mode
CAUTION
If the applicable static pressure does not match the static pressure mode, the static
pressure mode may be changed to another mode manually.
It is necessary to set up a static pressure mode for each usage of static pressure.
Static pressure can be set at site.
Relation between set values and static pressure are as the following table.
FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
Refer to the wired or wireless remote controller manual for detailed setting information.
Function Number Setting Number Setting Static Pressure
26
05 SP mode 05
06 SP mode 06
07 SP mode 07
08 SP mode 08
09 SP mode 09
.
.
.
.
.
.
27 SP mode 27
28 SP mode 28
29 SP mode 29
30 SP mode 30
31 Normal SP (Factory setting)
* Please refer to FAN PERFORMANCE CURVE within Design & Technical Data for the fea-
tures of each setting.
* If the Setting Number in AR96 is configured to “30”, the operation is the same as that in “29(SP
mode 29)”.
* If the Setting Number is con gured to be “31” Normal SP (factory setting), the static pressure
is 150Pa.