En-4
3.3.4. Mounting the duct
Follow the procedure in the following fi gure to install the ducts.
Inlet port fl ange
Inlet port fl ange
49-3/16 (1250)
49-3/16 (1250)
Outlet port fl ange
Outlet port fl ange
2-15/16 (75)
2-15/16 (75)
47-1/4 (1200)
47-1/4 (1200)
P5-7/8 (150) × 7
= 41-5/16 (1050)
P5-7/8 (150) × 7
= 41-5/16 (1050)
Unit : in (mm)
Unit : in (mm)
*13/16
(20)
*13/16
(20)
18-1/2
(470)
12-5/8
(320)
*4-15/16 (125)
13-3/4
(350)
11-7/16
(290)
9/16
(15)
9/16
(15)
1-3/8
(35)
3-9/16
(90)
6-5/16
(160)
14-9/16
(370)
7-1/2
(190)
3-9/16
(90)
9/16
(15)
6-5/16
(160)
12-5/8
(320)
13-3/4
(350)
*1
(25)
9/16
(15)
1-3/8
(35)
ARUH 72
ARUH 96
* Spacing between fl ange and safety drain pan.
CAUTION
To prevent people from touching the parts inside the unit, be sure to install grilles on
the inlet and outlet ports. The grilles must be designed in such a way that cannot be
removed without tools.
Set the external static pressure between 0 to 1.2 in WG (0 to 300 Pa).
If an intake duct is installed, take care not to damage the temperature sensor (the
temperature sensor is attached to the intake port fl ange).
Install the air inlet grille for air circulation. The correct temperature can not be
detected.
Unit
Outlet grille
(Locally purchased)
Inlet grille
(Locally purchased)
(Room)
Duct
(Locally purchased)
When connecting the duct, perform duct-insulation that is appropriate for the installing
environment.
Inappropriate insulation work may cause condensation on the surface of the insulating
material, and may lead condensation drip.
Be sure to install the air fi lter in the air inlet. If the air fi lter is not installed, the heat
exchanger may be clogged and its performance may decrease.
3.3.2. Installing hangers
Suspend the indoor unit by referring to the following fi gures.
AIR
AIR
AIR
AIR
AIR
AIR
17-11/16 (450)
21-5/8 (550)
62-1/2 (1587)
62-1/2 (1587)
55-1/2 (1410)
55-1/2 (1410)
2-9/16 (65)
2-9/16 (65)
Inlet port
Inlet port
Outlet port
Outlet port
Unit : in (mm)
Unit : in (mm)
27-9/16 (700)
27-9/16 (700)
25-11/16 (653)
25-11/16 (653)
ARUH 72
ARUH 96
Hanging bolt M10
(Locally purchased)
Special nut A
(Accessories)
Washer
(Accessories)
Special nut B
(Accessories)
Hanger
CAUTION
Fasten the unit securely with special nuts A and B.
3.3.3. Leveling
Use the procedure in the following fi gure to adjust the levelness.
(Front) (Side)
BBAA
Level
Level
Safety drain port
Main drain port
The side of the unit that holds the drain port
A
should be slightly lower than the opposite
side of the unit
B
. The slant should allow from 0 to 3/4 in (0 to 20 mm) of difference be-
tween
A
and
B
.
9365748237_IM.indb Sec1:49365748237_IM.indb Sec1:4 6/16/2015 4:24:46 PM6/16/2015 4:24:46 PM