En-13
Function
Function
number
Setting number
Default
Details
Control
switching
of external
heaters
61
00
Auxiliary
heater con-
trol 1
Sets the control method for the
external heater being used. For
details of the control method, see
the Design & Technical Manual.
01
Auxiliary
heater con-
trol 2
02
Heat pump
prohibition
control
03
Heater selec-
tion control
using outdoor
temperature 1
04
Heater selec-
tion control
using outdoor
temperature 2
05
Auxiliary
heater control
by outdoor
temperature 3
06
Auxiliary heat
pump control
07
Auxiliary heat
pump control
by outdoor
temperature 1
08
Auxiliary heat
pump control
by outdoor
temperature 2
09
Auxiliary heat
pump control
by outdoor
temperature 3
Operating
temperature
switching
of external
heaters
62
00 Setting 0
• Sets the temperature conditions
when the external heater is ON.
• For the temperature conditions,
see "Temperature conditions
when the external heater is ON".
For a more detailed explana-
tion, see the Design & Technical
Manual.
01 Setting 1
02 Setting 2
03 Setting 3
04 Setting 4
05 Setting 5
06 Setting 6
07 Setting 7
08 Setting 8
09 Setting 9
10 Setting 10
11 Setting 11
12 Setting 12
13 Setting 13
14 Setting 14
15 Setting 15
16 Setting 16
17 Setting 17
Auto mode
type (*3)
68
00
Single setpoint
auto mode
(traditional)
Switch the setting method of
auto mode to single or dual
(cooling/heating).
For heat pump systems, it is
necessary to set the master
indoor unit (by wired remote
controller).
01
Dual setpoint
auto mode
Deadband
value (*3)
69
00 0°F (0°C)
Choose the minimum temperature
between cooling and heating
settings (deadband) for Dual
setpoint auto mode (set in No. 68).
01 1°F (0.5°C)
02 2°F (1.0°C)
03 3°F (1.5°C)
04 4°F (2.0°C)
05 5°F (2.5°C)
06 6°F (3.0°C)
07 7°F (3.5°C)
08 8°F (4.0°C)
09 9°F (4.5°C)
(Forbidden) 70 00
7.4. Function setting
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
• Refer to “7.1. Setting the address” for indoor unit address and refrigerant circuit address
settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air tight
test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Function details
Function
Function
number
Setting number
Default
Details
Filter indica-
tor interval
11
00 Standard
Adjust the filter cleaning interval
notification. If the notification is too
early, change to setting 01. If the
notification is too late, change to
setting 02.
01 Longer
02 Shorter
Filter indica-
tor action
13
00 Enable
Enable or disable the filter indica-
tor. Setting 02 is for use with a
central remote controller.
01 Disable
02
Display only on
central remote
controller
(Forbidden) 20 00
(Forbidden) 23 00
(Forbidden) 24 00
Static pres-
sure
26
Refer to 7.3. Static pressure mode
Cool air
temperature
trigger
30
00 Standard
Adjust the cool air trigger
temperature. To lower the trigger
temperature, use setting 01. To
raise the trigger temperature, use
setting 02.
01 Adjust (1)
02 Adjust (2)
Heat air
temperature
trigger
31
00 Standard
Adjust the heat air trigger
temperature. To lower the trigger
temperature by 6 degrees C, use
setting 01. To lower the trigger
temperature by 4 degrees C, use
setting 02. To raise the trigger
temperature, use setting 03.
01 Adjust (1)
02 Adjust (2)
03 Adjust (3)
Auto restart
(*1)
40
00 Enable
Enable or disable automatic sys-
tem restart after a power outage.
01 Disable
Cool Air
Prevention
43
00 Super low
Restrain the cold airflow with mak-
ing the airflow lower when starting
heating operation. To correspond
to the ventilation, set to 01.
01
Follow the
setting on
the remote
controller
External
control
46
00 Start/Stop
Allow an external controller to start
or stop the system, or to perform
an emergency stop.
* If an emergency stop is
performed from an external
controller, all refrigerant systems
will be disabled.
* If forced stop is set, indoor unit
stops by the input to the external
input terminals, and Start/
Stop by a remote controller is
restricted.
01
Emergency
stop
02 Forced stop
Error report
target
47
00 All
Change the target for reporting er-
rors. Errors can either be reported
in all locations, or only on the
central remote controller.
01
Display only
on central
remote con-
troller
Fan set-
ting when
cooling
thermostat
OFF
49
00
Follow the
setting on
the remote
controller
When set to 01, the fan stops
when the thermostat is OFF in
cooling operation. Connection of
the wired remote controller (2-wire
type) and switching its thermistor
are necessary.
01 Stop
Switching
functions
for external
inputs and
external
outputs
terminals
(*2)
60
00 Mode 0
• Set this function when connecting
the VRF system to a ventilator,
economizer, humidifier, or other
external device.
• The connection terminal func-
tions can be changed depending
on the type of external device.
For details of the connection ter-
minal functions, see the Design
& Technical Manual.
01 Mode 1
02 Mode 2
03 Mode 3
04 Mode 4
05 Mode 5
06 Mode 6
07 Mode 7
08 Mode 8
9373385264-02_IM_L3.indb Sec1:139373385264-02_IM_L3.indb Sec1:13 9/24/2019 11:06:30 AM9/24/2019 11:06:30 AM