Outdoor unit address (Set B)
This function is available VR-II and V-II series.
Set the outdoor unit address for each outdoor unit.
Outdoor unit is preset "0" , at factory setting.
No change to this setting needed for 1 Outdoor Unit systems.
In case of 2 or 3 outdoor units connected in same refrigerant circuit, set the slave unit which
has installed farther from master unit to Slave2 setting "2".
0
Master
1
Slave1
2
Slave2
Outdoor unit address 0 1 2
SW SET3-1 OFF
SW SET3-2 OFF
SW SET3-1 OFF
SW SET3-2 ON
SW SET3-1 ON
SW SET3-2 OFF
Outdoor unit address 0 1 2
DIP SW
SET3-1 OFF OFF ON
SET3-2 OFF ON OFF
z
Number of slave unit (Set C)
This function is available VR-II and V-II series.
(Set at Master unit PCB only)
Set the number of slave unit on Master unit PCB.
Number of slave unit
0
SW SET3-3 OFF
SW SET3-4 OFF
Master
SW SET3-3 OFF
SW SET3-4 ON
Number of slave unit
1
Master Slave 1
SW SET3-3 ON
SW SET3-4 OFF
Number of slave unit
2
Master Slave 1 Slave 2
Number of slave unit 0 1 2
DIP SW
SET3-3 OFF OFF ON
SET3-4 OFF ON OFF
( . . . Factory Setting)
0
1
2
( . . . Factory Setting)
- (07 - 08) -
FUNCTION
SETTING
FUNCTION
SETTING