1-5-4. CONTROLLER EXTERNAL INPUT / OUTPUT FUNCTION
SUMMARY
CONTROLLER EXTERNAL INPUT FUNCTION
Central
controller
(Input function)
Dry
contact /
Apply
voltage
Function Specications
Emergency
stop
Batch on /
Batch off
Terminal
Signal
type
External power supply
Wire
size /
length
Allowable
voltage
Allowable
current
Touch
Panel
Controller
Dry
contact
(Screen icon)
(Screen icon)
TM201 (CH1-K1,K2)
[CN201 ↔ CN411]
Edge
- -
AWG22
Twist /
82 ft.
(25 m)
TM201 (CH1-K1,K2)
(CH2-K1,K 2)
[CN201 ↔ CN411]
Pulse *1
Apply
voltage
(Screen icon)
(Screen icon)
TM201 (CH1-K1,K2)
[CN201 ↔ CN412]
Edge
DC 12 [V]
10 mA or
less
TM201 (CH1-K1,K2)
(CH2-K1,K 2)
[CN201 ↔ CN412]
Pulse *1
Central
Remote
Controller
Dry
contact
(Screen icon)
(Screen icon)
CN6 (PIN1-2) Edge
- -
CN6 (Ch1:PIN1-2)
CN7 (Ch2:PIN1-2)
Pulse *1
Apply
voltage
(Screen icon)
(Screen icon)
CN11 (PIN1-3) Edge
DC 24 [V]
5 mA or
less
CN11 (Ch1:PIN1-3)
CN12 (Ch2:PIN1-3)
Pulse *1
*1 : Default setting is Edge signal, if you use pulse signal, must be set pulse signal from screen icon.
CONTROLLER EXTERNAL OUTPUT FUNCTION
Central Controller
(Output Function)
Dry
contact /
Apply
voltage
Function Specications
Operation
status
Error
status
Terminal
External power supply
Wire
size/ length
Allowable
voltage
Allowable
current
Touch
Panel
Controller
Apply
voltage
-
CN410
(PIN1-2)
DC 12 [V]
15 mA
or less
AWG22
Twist /
Max.
82 ft.
(25 m)
-
CN410
(PIN3-4)
Central
Remote
Controller
Apply
voltage
-
CN9
(PIN3-4)
-
CN9
(PIN1-2)
- (08 - 57) -