Number of outdoor units installed (Set L)
This function is available VR-II and V-II series.
The number of outdoor units installed in one refrigerant system must be set.
Set for all outdoor units.
1
2
3
2
3 3
Number of outdoor unit
1
Number of outdoor unit
2
Number of outdoor unit
3
SW SET5-1 OFF
SW SET5-2 OFF
SW SET5-1 OFF
SW SET5-2 ON
SW SET5-1 ON
SW SET5-2 OFF
Master
Master
Master
Slave 1
Slave 1 Slave 2
Number of outdoor unit 1 2 3
DIP SW
SET5-1 OFF OFF ON
SET5-2 OFF ON OFF
( . . . Factory Setting)
- (07 - 09) -
FUNCTION
SETTING
FUNCTION
SETTING