EasyManua.ls Logo

Fujitsu Airstage ASUB36TLAV1 - Page 872

Fujitsu Airstage ASUB36TLAV1
978 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1-4-2. EXTERNAL OUTPUT
Connector Output voltage Status
CN410
(Black)
Ch1 0 V All of indoor units "Stop"
Pins1-2 DC 12 V *17 At least one more indoor units "Operation"
Ch2 0 V Normal
Pins3-4 DC 12 V *17 Error
1
2
3
4
P.C. B
CN410
(Black)
Connected load
*18
connected unit
Connected load
*18
DC power supply
12 V
+
+
+
+
-
-
-
-
*19
*17: Provide a DC 12 V power supply. Select
a power supply capacity with an ample
surplus for the connected load.
Do not impress a voltage exceeding 12 V
across pins 1-2, and 3-4
*18: The allowable current is DC15mA or
less. Provide a load resistance such that the
current becomes DC 15 mA or less.
*19: Polarity is [+] for pins 1,3 and [-] for pins
2,4.
OPERATION STATUS (External output1)
The output for CN410(1-2) is ON when at least one more indoor units is operating.
The output is OFF when all of indoor units is stopped.
CN410(1-2)
Output
Indoor
units
Operation
Stop
12 V
0 V
ERROR STATUS (External output2)
The output for CN410(3-4) is ON when Error of at least one more indoor unit or outdoor unit or
Touch panel controller is generated.
CN410(3-4)
Output
Indoor unit or
Outdoor unit
or Touch panel
controller
Error
Normal
12 V
0 V
1-4-3. PARTS
Name and shapes Q'ty Model
EXTERNAL
CONNECT KIT
1 UTY-XWZXZA
- (08 - 52) -
EXTERNAL INPUT
& OUTPUT
EXTERNAL INPUT
& OUTPUT

Table of Contents