DIMENSIONS
211
241.6
288
2-Ø5
67
89.5
89.5
29
Ø28
For dust proof
bushing
4 - Ø5 For M4×20-mm screws
Ø28
For dust proof bushing
For M4×20-mm
screws
272 Hole pitch
95
Hole pitch
95
Hole pitch
Ø22.2 For conduit
(Unit : mm)
PACKING LIST
The following installation parts are supplied. Use them as required.
Name and shape Quantity Application
Installation manual 1
Cable tie
4
For mounting the power supply cable, remote controller
cable and transmission cable.
Screw
(M4 × 20 mm)
4 For mounting the network convertor.
Dust proof bushing 1 For connecting the power supply cable.
WIRING SPECIFICATIONS
Use Size Wire type Remarks
Power supply cable
Maximum 1.25 mm
2
60245 IEC 57 or equivalent
1 ø AC 208-240 V 50/60 Hz,
2 Wire + ground
(Always ground the unit)
Minimum 0.5 mm
2
Transmission cable
0.33 mm
2
(22AWG)
LEVEL4 (NEMA) non-polar 2 core,
twisted pair solid core Shielded
L
ON
W
ORKS
®
compatible cable
Remote controller cable
0.33 mm
2
(22AWG)
Polar 3 core
Use sheathed PVC cable or shielded
cable in accordance with the regional
cable standard.
External input / output
cable
0.33 mm
2
(22AWG)
Polar 2core, Twisted pair
Use shielded cable in accordance with
the regional cable standard.
Fuse capacity 3A
SPECIFICATIONS
Power supply 1ø AC208-240 V 50/60 Hz
Input Power (W) 6.5
Temperature(°C)
Operating 0 to 46
Packaged -10 to 60
Humidity (%) Packaged
0 to 95 (RH) ;
No condensation
Dimensions [H × W × D] (mm) 67 × 288 × 211
Weight (g) 1500
- (05 - 104) -
CONTROL
SYSTEM
CONTROL
SYSTEM