Multiple outdoor unit installation
NOTES:
Provide at least 8 in (200 mm) of space between the outdoor units if multiple units are in-
stalled.
When routing the piping from the side of an outdoor unit, provide space for the piping.
No more than 3 units must be installed side by side.
When 3 units or more are arranged in a line, provide the space as shown in the following ex-
ample when an obstruction is present also in the upward area.
When the upper space is open:
Unit: in (mm)
When there are obstacles at the rear only. When there are obstacles at the front only.
12 (300) or more
60 (1,500)
or more
When there are obstacles at the front and
rear.
20 (500)
or more
60 (1,500)
or more
When there is an obstruction in the upper space:
Unit: in (mm)
When there are obstacles at the rear and above.
60 (1,500)
or more
60 (1,500)
or more
20 (500) or more
Max. 11 (300)
4-1. Space requirement - (03-9) - 4. Installation space