EasyManua.ls Logo

Fujitsu AIRSTAGE J-IIIL - Page 33

Fujitsu AIRSTAGE J-IIIL
904 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Calculation method of outdoor unit capacity from capacity tables
(X, Y)
(X, Y)
(X, Y)
x
y
Capacity ratio of indoor units to outdoor unit, X (%)
Capacity of outdoor unit, Y (kBtu/h)
Equation for outdoor unit capacity calculation: Y = (Y
2
- Y
1
)/(X
2
- X
1
) × (X - X
1
) + Y
1
NOTE: Refer to "Cooling capacity table (Outdoor unit)
" on page 02-54 to find values of Y
1
and Y
2
using values of X
1
and X
2
.
Calculation example of 8 Ton outdoor units: AOU96RLAVL
115 61.2 6.51 78.3 8.35 79.2 8.35 82.8 8.35 83.7 8.35
Cooling capacity at rated condition: 96 kBtu/h (8 ton)
Total rated
capacity of
indoor unit
Outdoor
temperature
Indoor temperature
68°FDB/59°FWB
80°FDB/67°FWB 82°FDB/68°FWB 86°FDB/72°FWB 90°FDB/73°FWB
°FDB TC IP TC IP TC IP TC IP TC IP
105.6 (110%)
5
67.3 3.88 105.6 5.57 110.4 5.79 129.6 6.63 134.4 6.84
95 67.3 5.21 105.6 8.98 110.4 9.67 117.1 10.11 118.2 10.11
115 67.3 7.36 79.8 8.35 80.7 8.35 84.4 8.35 85.3 8.35
96.0 (100%)
5 61.2 3.61 96.0 5.15 100.4 5.34 117.8 6.11 122.2 6.31
95 61.2 4.82 96.0 7.74 100.4 8.29 114.5 10.11 115.6 10.11
Y!
Y"
X!
X"
Capacity ratio of indoor units to outdoor unit (%)
X
1
= 100
X = 102.1
X
2
= 110
Capacity of outdoor units (kBtu/h)
Y
1
= 100.4
Y
Y
2
= 110.4
Y = (110.4 - 100.4)/(110 - 100) × (102.1 - 100) + 100.4 = 102.5 kBtu/h
1-3. Capacity calculation method - (02-11) - 1. Model selection and capacity calculation
MODEL
SELECTION
MODEL
SELECTION

Table of Contents

Related product manuals