¢ Dimensions
Unit: in (mm)
3/8 (10)
2-11/16 (69)
3/16 × 13/16 = 3-1/8
(4 × 20 = 80)
Hole pitch
8-7/8 (225)
9-1/2 (241)
10-1/4 (260)
4-Ø3/16 (5)
2-Ø3/16 (5)
2-1/8 (54)
5-7/8 (150)
2-3/16 (55)
For M4 × 16 mm screws
Hole pitch
Hole pitch
For dust proof bushing
For M4 × 16 mm
screws
Hole pitch
2-3/16 (55)
3/4 (19)
5/8 (16)
Ø7/8 (22)
5-Ø1/2 (13)
For conduit
¢ S
pecifications
Power supply V 1 Ø AC 208—240
Power source frequency Hz 50/60
Input power W 2.0
Temperature
Operating °C 32 to 114.8 (0 to 46)
Packaged °C 14 to 140 (-10 to 60)
Humidity Packaged %
0 to 95 (RH)
No condensation
Dimensions (H × W × D) mm 2-1/8 × 10-1/4 × 5-7/8 (54 × 260 × 150)
Weight lb (g) 2 (1,100)
Fuse capacity A 2
W
iring specifications
Use Cable size Wire type Remarks
Power supply cable
20 to 16 AWG
(0.5 to 1.25 mm
2
)
60245 IEC 57 or equivalent
1 Ø AC 208—240 V 50/60 Hz,
2 wire + ground (Always ground
the unit)
Transmission cable
22 AWG
(0.33 mm
2
)
LEVEL 4 (NEMA)
Non-polar 2 core, twisted pair
solid core shielded
LonWorks
®
compatible cable
Modbus cable
26 to 16 AWG
(0.128 to 1.25 mm
2
)
AWG 16—26
3 Wire + Sheathed PVC cable
T
ransmission specifications
Transfer mode RTU mode
Communication method Half-duplex operation, Master/Slave method
Communication speed bps 9,600/19,200
Synchronous system Asynchronous communication method
Data bit bit 8
Parity even/odd/none
Stop bit bit 2 (no parity)/1
Network 3 wire RS485
Maximum cable length ft (m) 3,280 (1,000)
3-4. Modbus convertor for VRF (UTY-VMGX) - (05-134) - 3. Adaptor/Convertor units
CONTROL
SYSTEM
CONTROL
SYSTEM