Single-stage cooling and heating with dedicated fan speed relays
(Locally purchased)
Max.
16 units
Indoor unit
Fan
Thermostat convertor
AC 208/230 V
AC 24 V
Thermostat controller
Transformer*
AC 24 V
*: Install the transformer as necessary, per building code and manufacturer’s installation instruc-
tions. (Maximum power: 5.0 VA)
Terminal name Application
TC Common (In) from transformer
C Common to the thermostat controller
TR Power supply from transformer
R Power supply to thermostat controller
G3 Airflow High
G2 Airflow Medium
G1 Airflow Low
Y2 Cooling stage 2
Y1 Cooling stage 1
W2 Heating stage 2
W1 Heating stage 1
G Fan
NOTES:
For remote controller cable, 2-wire type and 3-wire type are available depending on the device
to be connected.
All wiring shown should be performed with 18 AWG thermostat wire.
Terminals to thermostat controller on Thermostat convertor support AC 20 to 30 V.
HIGH/MED/LOW fan signals are optional, and may not be available on all thermostat con-
trollers.
Signals for stage 2 are optional. W2 and Y2 terminals may not be used in single-stage ther-
mostats. To use the stage 2 signals, turn on the DIP switch SET3-1 on each convertor.
Up to 16 indoor units be controlled with a single thermostat controller. Multiple indoor units con-
nected to one Thermostat convertor are operable by the same operating setting.
Two or more types of VRF system, single model, or multi systems cannot be mixed together.
3-5. Thermostat convertor (UTY-TTRX) - (05-138) - 3. Adaptor/Convertor units
CONTROL
SYSTEM
CONTROL
SYSTEM