Function
Function
number
Setting number
Factory
setting
Details
Cool air
temperature
trigger
30
00 Standard Adjusts the cool air trigger temperature.
To make the trigger temperature lower than the
standard temperature, use setting “01”.
To make the trigger temperature higher than the
standard temperature, use setting “02”.
01 Adjust (1)
02 Adjust (2)
Heat air
temperature
trigger
31
00 Standard Adjusts the heat air trigger temperature.
To make the trigger temperature 6 degrees C lower
than the standard temperature, use setting “01”.
To make the trigger temperature 4 degrees C lower
than the standard temperature, use setting “02”.
To make the trigger temperature higher than the
standard temperature, use setting “03”.
01 Adjust (1)
02 Adjust (2)
03 Adjust (3)
Auto restart 40
00 Enable Enables or disables automatic system restart after a
power outage.
NOTE: Auto restart is an emergency function such
as for power failure etc. Do not start and
stop the indoor unit by this function in
normal operation.
Be sure to operate by the control unit,
converter or external input device.
01 Disable
Cool-air
prevention
43
00 Super low
Restrains the cold airflow with making the airflow
lower when starting heating operation. To correspond
to the ventilation, set to “01”.
01
Follow the setting
on the remote
controller
External
control
46
00 Start/Stop Allows an external controller to start or stop the
system, or to perform an emergency stop, or to
perform a forced stop.
If an emergency stop is performed from an
external controller, same refrigerant system will
be disabled.
If forced stop is set, indoor unit stops by the input
to the external input terminals, and Start/Stop by
a remote controller is restricted.
01 Emergency stop
02 Forced stop
Error report
target
47
00 All
Changes the target for reporting errors. Errors can
either be reported in all locations, or only on the wired
remote.
01
Display only on
central remote
control
Fan setting
when
cooling
thermostat
OFF
49
00
Follow the setting
on the remote
controller
When set “00”, indoor unit is continued operation
based upon central remote controller or
individual controller set.
Once indoor unit received signal from external
controller, indoor unit changed fan mode forcibly.
When set “01”, indoor unit is continued operation
based upon central remote controller or
individual controller set.
Once indoor unit received signal from external
controller, indoor unit stop forcibly.
Connection of the wired remote controller (2-wire
type or 3-wire type) and switching its thermistor
are necessary.
01 Stop
2-9. Function details - (07-97) - 2. Function settings
FUNCTION
SETTINGS
FUNCTION
SETTINGS