Function
Function
number
Setting number
Factory
setting
Details
Switching
functions for
external
inputs and
external
outputs
terminals
60
00 Mode 0 ♦ Sets this function when connected to external devices
such as the VRF system ventilator, economizer,
humidifier, etc.
The connection terminal functions can be changed
depending on the type of external device.
For details of the connection terminal functions, refer
to "Indoor unit" in Chapter 8. EXTERNAL INPUT AND
OUTPUT on page 08-
8.
NOTE: Inappropriate setting may cause an
external device malfunction. Confirm
whether all setting have been performed
appropriately according to the installing
condition.
01 Mode 1
02 Mode 2
03 Mode 3
04 Mode 4
05 Mode 5
06 Mode 6
07 Mode 7
08 Mode 8
Control
switching of
external
heaters
61
00
Auxiliary heater
control 1
♦
Sets the control method for external heater being
used.
For details of the control method, refer to "External
output" in Chapter 8. EXTERNAL INPUT AND
OUTPUT on page 08-5.
• Heater: external heater
• Heat pump: VRF outdoor unit
01
Auxiliary heater
control 2
02
Heat pump
prohibition control
03
Auxiliary heater
control by outdoor
temperature 1
04
Auxiliary heater
control by outdoor
temperature 2
05
Auxiliary heater
control by outdoor
temperature 3
06
Auxiliary heat
pump control
07
Auxiliary heat
pump control by
outdoor
temperature 1
08
Auxiliary heat
pump control by
outdoor
temperature 2
09
Auxiliary heat
pump control by
outdoor
temperature 3
2-9. Function details - (07-98) - 2. Function settings
FUNCTION
SETTINGS
FUNCTION
SETTINGS