SET3-1: Single-stage or Two-stage setting
SET3-1 Contents Factory setting
OFF Temperature setting: Single-stage
ON Temperature setting: Two-stage
When SET3-1 is set to “OFF” (Single-stage setting)
SET3-2: Cooling setting temperature
SET3-2
Cooling setting
temperature: °F (°C)
Remarks
Factory
setting
Stage 1
OFF 64 (18) Pattern 1
ON 68 (20) Pattern 2
SET3-3, 3-4: Heating setting temperature
SET3-3 SET3-4
Heating setting
temperature: °F (°C)
Remarks
Factory
setting
Stage 1
OFF OFF 86 (30) Pattern 1
OFF ON 81 (27) Pattern 2
ON OFF 75 (24) Pattern 3
ON ON 70 (21) Pattern 4
When SET3-1 is set to “ON” (Two-stage setting)
SET3-2: Cooling setting temperature
SET3-2
Cooling setting temperature: °F (°C)
Remarks
Factory
setting
Stage 1 Stage 2
OFF 68 (20) 64 (18) Pattern 1
ON 72 (22) 68 (20) Pattern 2
SET3-3, 3-4: Heating setting temperature
SET3-3 SET3-4
Heating setting temperature: °F (°C)
Remarks
Factory
setting
Stage 1 Stage 2
OFF OFF 81 (27) 86 (30) Pattern 1
OFF ON 77 (25) 82 (28) Pattern 2
ON OFF 75 (24) 79 (26) Pattern 3
ON ON 70 (21) 75 (24) Pattern 4
NOTE: Setting values are the limit temperature for cooling and heating.
Energy saving performance is improved in the order from cooling pattern 1 to 2
and heating pattern 1 to 4.
2-22. Thermostat convertor - (07-126) - 2. Function settings