Selecting the function
The function of the external input terminals is disabled at the time of factory shipment. Select the
function to be used by installer setting of application.
Turn on the power and select by installer setting after starting the application.
Emergency stop
Edge/Pulse
All on/All off
Electricity meter Pulse
I
nput signal type
The input signal type can be selected.
Edge
L
H
Emergency stop or All on
Ch1
L
H
Emergency stop reset or All off
Pulse
L
H
300 ms or more
Emergency stop or All on Ch1
Emergency stop reset or All off Ch2
L
H
50 ms or more
Electricity meter signal Ch1
When Edge is selected, only Ch1 can be used.
Control input function
In case of Edge input:
Terminal Channel no. Input signal Command
TM201 Ch1
Off → On All on / Emergency stop
On → Off All off / Normal
Ch1
I
ndoor unit
All on / Emergency stop
On
300 ms or more
Off
All off / Normal
4-1. Touch panel controller - (08-60) - 4. Controller
EXTERNAL INPUT
AND OUTPUT
EXTERNAL INPUT