Select outdoor units to match the total capacity of indoor units preliminarily
(Conrm the rated capacity ratio of indoor and outdoor units, the number of
connectable indoor units within limit)
Conrm if the capacity of outdoor units selected on previous process is listed
in Space saving combination or Energy efciency combination.
System capacity = Compensated capacity of outdoor units
END
Calculate actual capacity of each indoor unit by dividing
system capacity proportionally (Refer to 2-3-2)
Select Space saving combination
or Energy efciency combination.
System capacity = Total capacity of
indoor units at design temperature
Change to a larger
capacity of outdoor units
Actual capacity of indoor unit =
Capacity of indoor unit at design
temperature
Select outdoor units in the Space
saving combination.
A
Is the capacity of outdoor units selected listed in
Energy efciency combination?
Total capacity of indoor units at design
temperature ≥ Compensated capacity of
outdoor units
Actual capacity of indoor unit ≥ Heat load
Calculate the compensated capacity of outdoor units (Refer to 2-3-2)
Find outdoor unit capacity at design temperature ●
Calculate the compensated capacity ●
Compensation coefcient of pipe length (COOLING)
Compensation coefcient of pipe length and frosting/defrosting (HEATING)
≥
YES
YES
YES
NO
NO
NO
- (02 - 07) -
MODEL
SELECTION
MODEL
SELECTION