EasyManuals Logo

Fujitsu Airstage VR-II ARUV30TLAV User Manual

Fujitsu Airstage VR-II ARUV30TLAV
246 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #28 background imageLoading...
Page #28 background image
Push switch on
outdoor unit PCB
[ F2 ]
Setting mode
Setting Mode
ITEM
CODE No.
ITEM
CODE No.
Setting Function DefaultClassification
00
10
11
Pipe length setting
00
131-213ft.(40-65m)
01 0-131ft.(0-40m)
02
03
04
213-295ft.(65-90m)
295-394ft.(90-120m)
394-492ft.(120-150m)
00
01
02
03
Sequential start shift
21sec. Delay
42sec. Delay
63sec. Delay
Normal
00
01
02
03
04
Cooling capacity shift
Normal mode
Save energy mode +4
°
F(+2
°
C)
High power mode 1 -4
°
F(-2
°
C)
High power mode 2 -7
°
F(-4
°
C)
Forbidden
00
01
02
03
12
Heating capacity shift
Normal mode
Save energy mode -4
°
F(-2
°
C)
High power mode 1 +4
°
F(+2
°
C)
High power mode 2 +7
°
F(+4
°
C)
00
01
13,14,15 Forbidden
00
01
20 Switching between batch stop or
emergency stop
Emergency stop
Batch stop
00
01
00
01
02
03
22
Snow falling protection fan mode
23
Interval setting for snow falling
protection fan mode
Valid
Invalid
Standard (30min)
Short 1 (5min)
Short 2 (10min)
Short 3 (20min)
00
01
02
03
00
01
24
High static pressure mode
25,26,27 Forbidden
Standard
High static pressure 1 (equivalent to 0.12 in.WG /30Pa)
High static pressure 2 (equivalent to 0.32 in.WG /80Pa)
Forbidden
00
01
00
01
28
29
Change of unit Temperature
Change of unit Pressure
Celsius (
°C
)
Fahrenheit (
°F
)
MPa
psi
00
01
02
03
04
Change of
30 Energy saving level setting
function 2
Level 1 (stop)
Level 2 (operated at 40% capacity)
Level 3 (operated at 60% capacity)
Level 4 (operated at 80% capacity)
Level 5 (operated at 100% capacity)
00
01
00
01
32,33 Forbidden
35
36
Presence of heater selection
control using outdoor temperature *1
Yes
No
00
01
02
03
04
05
06
07
08
Outdoor temperature zone
boundary temperature A*1
-4.0
°
F(-20
°C)
-0.4
°
F(-18
°C)
-3.2
°
F(-16
°C)
6.8
°
F(-14
°C)
10.4
°
F(-12
°C)
14.0
°
F(-10
°C)
17.6
°
F(-8
°C)
21.2
°
F(-6
°C)
24.8
°
F(-4
°C)
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
37 Outdoor temperature zone
boundary temperature B*1
42.8
°
F(6
°C)
14.0
°
F(-10
°C)
17.6
°
F(-8
°C)
21.2
°
F(-6
°C)
24.8
°
F(-4
°C)
28.4
°
F(-2
°C)
32.0
°
F(0
°C)
35.6
°
F(2
°C)
39.2
°
F(4
°C)
42.8
°
F(6
°C)
46.4
°
F(8
°C)
50.0
°
F(10
°C)
53.6
°
F(12
°C)
57.2
°
F(14
°C)
60.8
°
F(16
°C)
64.4
°
F(18
°C)
Install
Correction
Change of
function 1
01-22

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu Airstage VR-II ARUV30TLAV and is the answer not in the manual?

Fujitsu Airstage VR-II ARUV30TLAV Specifications

General IconGeneral
BrandFujitsu
ModelAirstage VR-II ARUV30TLAV
CategoryAir Conditioner
LanguageEnglish

Related product manuals