Check point 6. Check strainer
Strainer normally does not have temperature difference between inlet and outlet as shown be-
low.
Pipe (In) Pipe (Out)
If there is a difference like shown below, there is a possibility of inside clogged. In this case,
replace the strainer.
Pipe (In) Pipe (Out)
4-3. Outdoor unit Electronic Expansion Valve (EEV) - (03-62) - 4. Service parts information
TROUBLESHOOTING
TROUBLESHOOTING