01-06
Setting
Fan mode
Lo mode
S-Lo mode
Indoor heat exchanger
temperature
Indoor heat exchanger
temperature
The maximum value of the indoor fan speed is set as shown in Figure 6, based on the detected
temperature by the indoor heat exchanger sensor on heating mode.
( Fig.6 : Cool Air Prevention Control )
6-2. For AR Type
6-3. For AU Type
Indoor heat exchanger
temperature
Indoor heat exchanger
temperature
When the compressor operates, the maximum value of the indoor fan speed is set as shown in Figure 7,
based on the detected temperature by the indoor heat exchanger sensor on heating mode.
When the compressor does not operate, the indoor fan motor operates [S-Lo] mode.
( Fig.7 : Cool Air Prevention Control )
< [Hi] setting >
Hi
Me+
Lo
Cool air
prevention
Indoor heat exchanger
temperature
Indoor heat exchanger
temperature
< The other of [Hi] setting >
S-Lo
Lo (Qu)
Cool air
prevention
Setting
FAN mode
S-Lo
90°F(32°C)
93°F(34°C)
99°F(37°C)
86°F(30°C)
86°F(30°C)
91.4°F(33°C)
86°F(30°C)
99°F(37°C)
102.2°F(39°C)
107.6°F(42°C)
75.2°F(24°C)
93°F(34°C)
90°F(32°C)
75.2°F(24°C)
102.2°F(39°C)
86°F(30°C)
99°F(37°C)