Forced thermostat off function
Rotary SW on External
Input and Output PCB
External input Input signal Command
2
B
C
External Input and Output PCB CN313
Off → On Thermostat off
On → Off Normal operation
On
Off
On
Off
Compressor
Room temp.
Set temp.
Input
¢
Control output function
Operation/Stop status
Rotary SW on External
Input and Output PCB
External output
Output
signal
Command
1
B
C
D
External Input and Output PCB CN310
Off → On Operation
On → Off Stop
The output is low when the unit is stopped.
Operation
Stop
On
Off
CN310
Indoor unit
Error status
Rotary SW on External
Input and Output PCB
External output
Output
signal
Command
1
C
External Input and Output PCB
CN311
Off → On Error
On → Off Normal
D CN312
Off → On Error
On → Off Normal
The output is ON when an error is generated for the indoor unit.
Error
Normal
On
Off
CN311―312
Indoor unit
- 27 -
8-4. Details of function 8. External input and output
WALL MOUNTED
ASUH09-12LPAS
WALL MOUNTED
ASUH09-12LPAS