Refer to error code table.
Compressor Thermistor Error
D
C
Compressor temperature thermistor
Compressor temperature thermistor short detected
Compressor thermistor open detected
1. Connector connection failure, open
2. Thermistor failure
3. Main PCB failure
OK
OK
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information 8".
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN62:3-4) voltage value = 5V
Remove the thermistor from Main PCB, check the voltage.
Compressor temperature thermistor (CN62:3-4)
If the voltage does not appear, replace Main PCB, and execute
the check operation again.
02-16
Trouble shooting 13
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
CN62
THERMISTOR
(COMP SHELL1)
THERMISTOR
(DIS.TEMP.1)
BLACK
BLACK
BLA
C
K
BLA
C
K
1 2 3 4
1 2 3 4

Other manuals for Fujitsu ARTG30LHTA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ARTG30LHTA and is the answer not in the manual?

Fujitsu ARTG30LHTA Specifications

General IconGeneral
BrandFujitsu
ModelARTG30LHTA
CategoryAir Conditioner
LanguageEnglish

Related product manuals