Heat pump prohibition control
Perform heating by external heater only. Indoor unit is continuous thermostat off.
Compact cassette type
Operation Condition
Heater on
Heater is on as shown in following diagram of heating
temperature.
Heater off
Heater is off as shown in following diagram of heating
temperature.
Other than heating mode
Error occurred
Forced thermostat off
Slim duct type
Operation Condition
Heater on
Heater is on as shown in following diagram of heating
temperature.
Heater off
DIP-SW101-3 On Heater is off as shown in following diagram of heating
temperature.
Other than heating mode
Error occurred
Forced thermostat off
Fan stop protection
Indoor unit fan
setting for
external heater
Enabled
DIP-SW101-3 Off Heater is off as shown in following diagram of heating
temperature.
Other than heating mode
Error occurred
Forced thermostat off
Indoor unit fan
setting for
external heater
Disabled
Temperature of heater on (Thon): Adjustable by function number 62 (Operating temperature
switching of external heaters).
All control temperatures will shift by adjusting “Thon”.
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
Off
On
Tr-Ts
Tr-Ts (=Thon) ≤ -0.9°F (-0.5°C)
Tr-Ts ≥ 0.9°F
(0.5°C)
- 104 -
11-4. Details of function 11. External input and output (Compact cassette type and slim duct type indoor unit)
MULTI-SPLIT TYPE
5-unit type
MULTI-SPLIT TYPE
5-unit type

Table of Contents

Other manuals for Fujitsu ASUH18LPAS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASUH18LPAS and is the answer not in the manual?

Fujitsu ASUH18LPAS Specifications

General IconGeneral
BrandFujitsu
ModelASUH18LPAS
CategoryAir Conditioner
LanguageEnglish

Related product manuals