Outdoor Unit High Pressure Value and Outdoor Total Electric Current Curve (Heating)
Model Name : ASYA07/09/12LCC
[Condition]
Ambient
temperature
Indoor 15 - 23degC, Outdoor 2 - 12degC
Refrigerant
amount
Standard amount
Piping 7.5m (Height difference 1m)
Power
voltage
50Hz - 230V
Operation
condition
TEST mode (Heating), Hi Fan, Lower direction, Front air flow
Measuring
method
Caution
Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Heating mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor High Pressure Curve
AS*9LSACW series
ASYA12LCC
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
AS*9LSACW series ASYA12LCC
outdoor unit overall current with the current clamp meter at Power Cable.
1.8
2
2.2
2.4
2.6
2.8
3
0 5 10 15
outdoor ambient temparature C
High-pressure of outdoor unit MPa
15 C
20 C(Indoor inlet tempe)
23 C
3.00
3.50
4.00
4.50
0 5 10 15
outdoor ambient temparature C
Outdoor total electric current A
15 C
20 C(Indoor inlet temp)
23 C
length
08-03
2
2.2
2.4
2.6
2.8
3
3.2
3.4
0 2 4 6 8 10 12 14
Outdoor ambient temparature [degC]
High-pressure of outdoor unit
[MPa]
15degC
20degC
(Indoor ambient temp. )
23degC
4
4.5
5
5.5
6
6.5
7
0 2 4 6 8 10 12 14
Outdoor ambient temparature [degC]
Outdoor total electric current [A]
15degC
20degC
(Indoor ambient temp. )
23degC