Figure 54 Unit Installation Area
ETERNUS DX
(1)
(2)
(3)
(4)
Rear door of the rackFront door of the rack Rack pillars
Rack rails
Table 33 Specifications for the Unit Installation Area
Specification Condition
(1) Rack front space
(Space between the fixed part of the
ETERNUS DX on the
front side and the front of the rack)
40mm or more
(2) Mount bracket length
(Size between each end of the front and rear rack pillars)
685mm or more
775mm or less
(3) Rack space
(Space between the fixed part of the
ETERNUS DX on the
front side and the rear of the rack)
890mm or more
(4) Rack mount kit installation area 482mm or more
(recommended)
■
Placement Requirements
When determining service areas, refer to the manual of the rack that is to be used.
Make sure to perform the installation according to the placement requirements described in "
Installation Specifi-
cations" (page 10) and "Installation Environment" (page 32).
2. Rack Installation Specifications
Installable Racks
79
FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems
Site Planning Guide
Copyright 2020 FUJITSU LIMITED
P3AM-9422-13ENZ0