● For Direct (No Power Distribution Unit) Connections
The following diagram shows a power supply connection example when no power distribution units are used.
Figure 17 Example of a Power Supply Connection When a Power Distribution Unit Is Not Used
Line
0
Line
1
CP CP
PSU
PSU
PSU
PSU
PSU
PSU
Drive enclosure
Controller
enclosure
ETERNUS DX
Distribution board
Drive enclosure
Distribution board
↓To power supply facility
↑To power supply facility
PSU: Power Supply Unit
CP: Circuit Protector
•
Only connect the ETERNUS DX
to circuit protectors.
1. ETERNUS DX Installation
Outlet/Socket Specifications
40
FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems
Site Planning Guide
Copyright 2021 FUJITSU LIMITED
P3AM-7632-18ENZ0