Figure 31 Unit Installation Area
ETERNUS DX
(1)
(2)
(3)
(4)
Rear door of the rackFront door of the rack Rack pillars
Rack rails
Table 23 Specifications for the Unit Installation Area
Specification Condition
Conditions when high-density drive
enclosures are installed
(1) Rack front space
(Space between the fixed part of the
ETERNUS DX
on the front side and the front of the rack)
40mm or more 80mm or more
(2) Mount bracket length
(Size between each end of the front and rear rack
pillars)
685mm or more
775mm or less
685mm or more
750mm or less
(3) Rack space
(Space between the fixed part of the
ETERNUS DX
on the front side and the rear of the rack)
830mm or more 915mm or more
(4) Rack mount kit installation area 482mm or more
(recommended)
490mm or more
■
Placement Requirements
When determining service areas, refer to the manual of the rack that is to be used.
Make sure to perform the installation according to the placement requirements described in "
Installation Specifi-
cations" (page 7) and "Installation Environment" (page 28).
2. Rack Installation Specifications
Installable Racks
55
FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems
Site Planning Guide
Copyright 2021 FUJITSU LIMITED
P3AM-7632-18ENZ0